A Power Control Centre (PCC) panel is a low-tension (LT) switchgear assembly used to receive power from a source (mains, DG set, or transformer) and distribute it to various sub-feeders and motor loads in an industrial or commercial facility. It acts as the nerve Centre of power distribution and motor control.
TECHNICAL SPECIFICATION
- Incoming supply = 3 Phase, 4 wire & 1 Phase 2wire
- Installation = Indoor & Outdoor
- Rated Operation Voltage = 3Phase,415V ± 10% AC
- Rated Control voltage = 230V AC/24 VDC
- Rated Service Voltage = 500 V AC
- Rated Insulation Voltage = 800 V
- Fault level Bus Bar = 50kA for 1 sec
- Rated Frequency = 50Hz +/- 5%
- Rated Current = Up to 2500 Amp
- Combined Variation = ± 10%
- Dry Power Frequency
Withstand Voltage = 2.5KV
- Short Circuit Level = 50 KA
- Temperature rise = 40 oC above Ambient 45 oC
- Form of segregation = Form-3b/Form-4b
- Degree of Protection = Up to IP 54
- Metal Sheet Thickness = 1.6mm/2mm/3mm
- External Surface Protection = Epoxy Powder Polymerized at High Temperature
- Painting Thickness = more than 60 micron
- Standard Colour = Grey RAL 7035
- Bus bars = Aluminium / Copper
- Bus bar Supports = SMC / DMC / FRP
- Standard Compliance = IS 8623, IS 13947, IEC 61439
- Standard Depth of
Switchboards = 400/600 mm
- Standard Feeder Width = 400/500/600 mm
- Mounting = Floor mounted
- Door = Hinged Type at Front and rear.
- Cable Entry = top & bottom
- Name Plates = Aluminum Sheet (White Letters on Black Background)
- Control wiring & Colour
Code = 1100V PVC insulated copper wires; 1.5 sq.mm for control circuit (Grey & Black); 2.5 sq.mm for CT circuit (Red, Yellow, Blue for phase & Earth Green)
- Power terminals =BUSBAR
- Control terminals = 2.5sq. mm Clip on type
- Earthing = AL Bus will be provided.
- Routine Test = All routine tests as per the specification and relevant standards will be carried out.